For Commercial & Industrial Hire

600kW Boiler Containerised Hire

600kW Boiler Containerised Hire: The 600kW containerised boiler is a high-capacity temporary heating solution available for short-term or long-term hire. Engineered for large-scale commercial and industrial applications, this fully containerised unit provides rapid deployment, minimal installation time, and reliable performance in harsh environments.

Designed for temporary heating and hot water support, the system delivers powerful output through a WaterMark-certified heat exchanger, making it ideal for process heating, hydronic heating, shutdown works, plant upgrades, and emergency hot water replacement. With flexible fuel connection options and compatibility with bulk fuel tanks, this rental boiler ensures continuous operation throughout your project.

Its rugged 20ft Hi-Cube container enclosure keeps the equipment weatherproof, secure, and tidy on site, while forklift pockets and ISO lifting points allow easy relocation. Whether you require temporary capacity, emergency backup, or a scalable heating solution, this 600kW rental boiler provides safe, dependable, high-volume hot water wherever it’s needed.

Applications

  • Industrial shutdowns and plant maintenance
  • Emergency boiler replacement
  • Temporary hot water supply for commercial facilities
  • Construction site heating and commissioning
  • Mining and remote site operations
  • Process heating for manufacturing
  • Seasonal HVAC load support
  • Potable hot water supply via integrated heat exchanger

Features & Benefits

  • High-capacity 1000kW heating for temporary applications, ideal for shutdowns, seasonal demand, and emergency replacement
  • Fast, simple installation to minimise downtime and enable rapid deployment
  • WaterMark-certified heat exchanger for safe, compliant potable hot water use
  • Reliable diesel-fired boiler designed for continuous operation throughout the rental period
  • Alternative natural gas fuel train can be offered as an option
  • Compatible with bulk fuel tanks for extended, uninterrupted operation
  • Rugged, containerised design for secure, weatherproof performance in harsh environments whilst complying to Australian standards for natural gas operation with high- and low-level ventilation louvres.
  • Easy transport and relocation with forklift pockets and ISO container lifting points
  • Fully self-contained system, reducing the need for additional site infrastructure
  • Flexible configuration options (with or without external pump) to suit site requirements
  • Built-in control interface for easy integration and monitoring
  • Comprehensive alarm system to enhance safety and operational reliability
  • Visual alarm tower and digital hot water temperature readout

Technical Info

  • Model: BC600 (600kW Containerised Boiler)
  • Type: Non-condensing fire tube boiler
  • Nominal Heating Capacity: 581–600 kW
  • Maximum Working Pressure: 500 kPa
  • Water Content: 635 litres

Electrical Requirements:

  • Voltage: 400V ±10% (3-phase + Neutral + Earth)
  • Frequency: 50 Hz
  • Max Current: 24.5 A (excluding external pump)
  • Connection: 63A Ceeform inlet
  • External Pump Outlet: 63A Ceeform
  • Note: Hardwiring/direct boiler connection is not permitted

Fuel System:

  • Fuel Type: Diesel
  • Fuel Consumption: 55.1 L/hr (max)
  • Control Type: Hi/Lo

Control Interface:

Inputs:

  • Start
  • Stop
  • Flow rate

Outputs:

  • Supply water temperature
  • Return water temperature

Alarms:

  • Over temperature
  • Low water
  • Low fuel
  • Flame failure
  • Emergency stop (E-stop open)

 

Performance

Primary Circuit:

  • Flow Rate: 7 L/s
  • Operating Temperature: 70–90°C

Secondary Circuit:

  • Flow Rate: 4–7 L/s
  • Operating Temperature: 60–80°C

Heat Exchanger:

  • Capacity: 600 kW @ 1000Kpa
  • WaterMark approved (potable water compliant)
  • Stable temperature control under varying load conditions

System Behaviour:

  • Maintains consistent output under fluctuating load
  • External pump (optional) supports secondary circuit performance

Physical Info

  • Container Type: 20ft Hi-Cube
  • Fully enclosed, weatherproof design
  • Forklift pockets and ISO container lifting points

Flue

  • Material: 316 stainless steel
  • Diameter: 350 mm
  • Discharge: Vertical
  • Supplied without external flue
  • Clearance required for safe installation and operation

Power Requirements

  • 400V ±10%
  • 3-phase + Neutral + Earth
  • 50 Hz
  • 63A Ceeform connection
  • Max current draw: 24.5 A (excluding external pump)

Accessories

  • 5-lane crossover
  • 63Amp 3-phase extension leads
  • Hot water pipework and hose
  • Hot water pumps (external pump optional for secondary circuit)
  • External bulk fuel tanks
  • High-capacity diesel burner, can be interchanged for NG burner train
  • Flue components (optional extensions)

Product Enquiry Form